OIL / WINDING TEMPERATURE INDICATORS ....
View
other oil / winding temperature indicators ...
SCIENTIFIC CONTROLS
Mechanical Instruments are incorporates proven design features
acquired from many years of experience in providing Temperature
Indicators/Controllers for Power & Distribution Transformers
Oil Temperature Indicator
: The Oil Temperature Indicator (OTI) measures the Top
oil Temperature. It is used for control and protection for all
transformers.
Winding Temperature Indicator
: The Winding is the component with highest temperature
within the transformer and, above all, the one subject to the
fastest temperature increase as the load increases. Thus to have
total control of the temperature parameter within transformer,
the temperature of the winding as well as top oil, must be measured.
An indirect system is used to measure winding temperature, since
it is dangerous to place a sensor close to winding due to the
high voltage. The indirect measurement is done by means of a Built-in
Thermal Image.
Winding Temperature Indicator is equipped with
a specially designed Heater which is placed around the operating
bellows through which passes a current proportional to the current
passing through the transformer winding subject to a given load.
Winding Temperature is measured by connecting the CT Secondary
of the Transformer through a shunt resistor inside the Winding
Temperature Indicator to the Heater Coil around the operating
Bellows. It is possible to adjust gradient by means of Shunt Resistor
In this way the value of the winding temperature indicated by
the instrument will be equal to the one planned by the transformer
manufacturer for a given transformer load.
SALIENT FEATURES :
- No external power supply required for indication or operation
- Liquid in metal expansion provides self powered system
- Fully compensated for ambient temperature changes in line
& case
- Built-in Thermal imaging for transformer 'Hot Spot' temperature
indication (in case of WTI)
- Weather proof case for outdoor services (IP55)
- Panel mount or Projection mounting (varies with Different
Models)
- Maximum capillary length of 15 mtrs. (varies with Different
Models)
- Up to 4 control switches are available (varies with Different
Models)
- Maximum indicating pointer facility Switch Test Knob facility
- Remote Indication & Data acquisition facility
- Sealed system which requires no trimming or periodic site
adjustments.
A ) MERCURY SWITCH TYPE OIL TEMPERATURE INDICATORS
(OTI) / WINDING TEMPERATURE INDICATORS (WTI) INSTRUMENTS
| Model
No. : 2002
This is a high performance micro switch
instrument with +/- 2°C accuracy. capable of temperature
monitoring, indication & control, for the protection
of Transformers from 1 MVA to 10 MVA rating. |
|
| Technical Data : |
| Dial Diameter |
: |
118 mm Segment Dial |
| Angular Sweep |
: |
60° |
| Range |
: |
0-120°C, 0-150°C, 20-140°C &
30-150°C |
| Accuracy |
: |
+/-2°C |
| Graduations |
: |
2°C per division |
| |
|
|
| Electrical Connections : |
All line to body
(Earth) High Voltage
Breakdown Tested |
: |
2.5 KV AC, 50Hz for 60 seconds |
| Terminal Type |
: |
WAGO Terminals Press Fit Type |
| |
|
|
|
| Switch Configurations : |
|
| Maximum Number of Switches |
: |
4 |
|
| Switch Type |
: |
Dry electrode mercury in glass |
|
| Switch Rating |
: |
5A AC/DC at 250V |
|
| Switches |
: |
Normally Open Type |
|
| Adjustable Range |
: |
10-90% of Full Scale Range |
|
| Switch Differential |
: |
6-90°C (Close to Open & Vice Versa) |
|
| Switch Accuracy |
: |
+/-2.5°C of Set Value |
|
| Instrument Case |
: |
Weatherproof pressure die-cast Aluminum
Alloy Casting with epoxy coated tall sides.
Protective Class IP55 as per IS 13947 Part II. |
|
| Capillary Entry |
: |
Bottom or Top of the case |
|
| Cap. Length |
: |
Up to 15 Meters |
|
| Cap. Tubing |
: |
Capillary line protected by flexible Stainless
Steel Armour and additional Stainless Steel Armour to reinforce
at the entry to the case. |
|
| |
|
|
|
| Standard Fittings : |
- Switch Testing Knob
- Resettable Maximum Pointer
- Anti-Vibration Mounting Grommets (for Projection Mounting)
|
|
|
Model No. : 2003
This is a high performance, precision
mercury switch instrument with +/- 2.5°C accuracy, capable
of temperature monitoring, indication & control, for
the protection of Transformers from 5 MVA rating.

|
Technical
Data : |
| Dial Diameter
|
: |
150 mm (6") Round
Type |
| Angular Sweep |
: |
270° |
| Range |
: |
0-150°C |
| Accuracy |
: |
+/-2.5°C |
| Graduations |
: |
2°C per division |
| |
|
|
| Electrical
Connections : |
Cable
Conductor Size |
: |
1 sq. mm. |
| Oil Temperature |
: |
4 Core Copper
Cable for Switch Connections (Length as per Customer
Requirement) |
Winding
Temperature Indicator |
: |
4 Core for Switch connections
and 2 Core Copper Cable for CT Connection Length as
per Customer Requirement) |
All Line
to Body (Earth) High Voltage Breakdown Tested |
: |
2.5 KV AC, 50Hz. for 60
Seconds |
| |
|
|
| Switch Configurations
: |
Maximum
Number of Switches |
: |
2 |
| Switch Type |
: |
Heavy Duty Dry Electrode
Mercury in Glass |
| Switch Rating |
: |
2A AC/DC at 250V ±
10% |
| Switches |
: |
Normally Open Type |
| Adjustable
Range |
: |
10-90% of Full Scale Range |
| Switch Differential
|
: |
8°C Fixed |
| Switch Accuracy |
: |
+/-2.5°C of Set Value |
| Contact Type |
: |
Switch Contacts are Potential
Free |
| Instrument
Case |
: |
Weatherproof Aluminum
Alloy Casting with epoxy coated at all sides. Suitable
for outdoor mounting - Protective Class IP55 as per
IS 13947 Part II. |
| Capillary Entry
|
: |
Bottom or Top of the case |
| Cap. Length |
: |
Up to 6 Meters |
| Cap. Material |
: |
Capillary line protected
by flexible Stainless Steel Armour |
| |
|
|
| Standard Fittings
: |
- Switch Testing Knob
- Resettable Maximum Pointer
- Anti-Vibration Mounting
|
|
B ) MICRO SWITCH TYPE OIL TEMPERATURE INDICATORS
(OTI) / WINDING TEMPERATURE INDICATORS (WT) INSTRUMENTS
| Model
No. : 2004
This is a high performance instrument with
+/- 2°C accuracy. capable of temperature monitoring,
indication & control, for the protection of Transformers
from 1 MVA to 10 MVA rating. |
|
| Technical Data : |
| Dial Diameter |
: |
118 mm Segment Dial |
| Angular Sweep |
: |
60° |
| Range |
: |
0-120°C, 0-150°C, 20-140°C &
30-150°C |
| Accuracy |
: |
+/-2°C |
| Graduations |
: |
2°C per division |
| |
|
|
| Electrical Connections : |
All line to body
(Earth) High Voltage
Breakdown Tested |
: |
2.5 KV AC, 50Hz for 60 seconds |
| Terminal Type |
: |
WAGO Terminals Press Fit Type |
| |
|
|
|
| Switch Configurations : |
|
| Maximum Number of Switches |
: |
4 |
|
| Switch Type |
: |
Heavy Duty Micro Switch |
|
| Switch Rating |
: |
5A at 240V ± 10% AC & 0.5 A at
220 V ± 10% DC |
|
| Switches |
: |
Normally Open Type |
|
| Adjustable Range |
: |
10-90% of Full Scale Range |
|
| Switch Differential |
: |
5°C Fixed |
|
| Switch Accuracy |
: |
+/-2.5°C of Set Value |
|
| Contact Type |
: |
Switch Contacts are Potential Free |
|
| Instrument Case |
: |
Weatherproof pressure die-cast Aluminum
Alloy Casting with epoxy coated tall sides.
Protective Class IP55 as per IS 13947 Part II.
|
|
| Capillary Entry |
: |
Bottom or Top of the case |
|
| Cap. Length |
: |
Up to 15 Meters |
|
| Cap. Tubing |
: |
Capillary line protected
by flexible Stainless Steel Armour and additional Stainless
Steel Armour to reinforce at the entry to the case. |
|
| |
|
|
|
| Standard Fittings : |
- Resettable Maximum Pointer
- Anti-Vibration Mounting Grommets (for Projection Mounting)
|
|
|
Model No. : 2031
This is a high performance, precision
micro switch instrument with +/- 2.50C accuracy, capable
of temperature monitoring, indication & control, for
the protection of Transformers from 5 MVA rating.
 |
Technical
Data : |
| Dial Diameter
|
: |
150 mm Segment Dial |
| Angular Sweep |
: |
60° |
| Range |
: |
0-150°C |
| Accuracy |
: |
+/-2.5°C |
| Graduations |
: |
2°C per division |
| |
|
|
| Electrical
Connections : |
| Cable
Conductor Size |
: |
1 sq. mm. |
| Oil Temperature |
: |
4 Core Copper
Cable for Switch Connections (Length as per Customer
Requirement) |
|
Winding
Temperature Indicator |
: |
4 Core for Switch connections
and 2 Core Copper Cable for CT Connection Length as
per Customer Requirement) |
All Line
to Body (Earth) High Voltage Breakdown Tested |
: |
2.5 KV AC, 50Hz. for 60
Seconds |
| |
|
|
| Switch Configurations
: |
Maximum
Number of Switches |
: |
2 |
| Switch Type |
: |
Heavy Duty Micro Switch |
| Switch Rating |
: |
5A at 240V ± 10%
AC & 0.5 A at 220 V ± 10% DC |
| Switches |
: |
Normally Open Type |
| Adjustable
Range |
: |
10-90% of Full Scale Range |
| Switch Differential
|
: |
5°C Fixed |
| Switch Accuracy |
: |
+/-2.5°C of Set Value |
| Contact Type |
: |
Switch Contacts are Potential
Free |
| Instrument
Case |
: |
Weatherproof Aluminum
Alloy Casting with epoxy coated at all sides. Suitable
for outdoor mounting - Protective Class IP55 as per
IS 13947 Part II. |
| Capillary Entry
|
: |
Bottom or Top of the case |
| Cap. Length |
: |
Up to 6 Meters |
| Cap. Material |
: |
Capillary line protected
by flexible Stainless Steel Armour |
| |
|
|
| Standard Fittings
: |
- Resettable Maximum Pointer
- Anti-Vibration Mounting.
|
|
|